Potential alarm AP100 and AP200 (ADF or Standard)
Réf. DIP-087
Autonomous cathodic-protection potential monitoring alarm. The AP200 adds a remote relay output. 10-year battery life, standard (IP66) or flameproof (Ex II 2 G) versions.
Potential alarm AP100 and AP200 (ADF or Standard): overview
The AP100 and AP200 potential alarms are autonomous devices that allow personnel with no particular cathodic-protection knowledge to visually check that their system is working correctly. The AP200 features a volt-free relay contact to report a fault remotely.
To guarantee that a fault is observed, an acknowledgement without opening the enclosure is required to return to the normal state. Thanks to the embedded very-low-power and optical technologies, battery life reaches ten years in normal mode and at least one year in alarm mode.
This product is particularly recommended for monitoring buried tanks, service stations, hazardous areas and isolated sites with no power source. Two versions are available: standard (ABS housing, IP66) and flameproof ADF (marine aluminium alloy, Ex II 2 G – Eexd IIC T6) for gas zones 1 and 2.
Choosing in two questions
First question: should the fault be seen on site or reported? A regularly visited site only needs the AP100 and its indicator; an isolated site, or one monitored from a control room, calls for the AP200 and its reporting relay. Second question: is the site ATEX-classified? If so, the flameproof ADF version is required; otherwise, the standard version in an ABS housing is enough.
Why a self-powered alarm
Battery-powered, the alarm depends neither on the mains nor on the rectifier it monitors: it stays reliable precisely when the installation fails. The ten-year battery life in normal mode means it can be installed on sites without power and left alone between maintenance visits.
Potential alarm AP100 and AP200 (ADF or Standard): technical specifications
| Power supply | 3.6 V – 16.4 Ah lithium battery (D case), maximum service life 10 years |
| Consumption | 70 µA in normal mode, 1.5 mA in alarm mode |
| Battery life | 10 years in normal mode, at least 1 year in alarm mode (new battery) |
| Alarm output (AP200) | Monostable normally-open relay, 12 V max, 0.5 W |
| Electrode input (RE/structure) | 5 V peak max, 3.3 V mean max; measurement error ±50 mV max at 5 V |
| Indicator | Red (λd 626 nm), 12,000 to 16,000 mcd, viewing angle 80° direct / 140° indirect |
| Standard version | Grey ABS housing RAL 7035 with transparent cover, 121 × 186 × 86 mm, 800 g, IP66 / NEMA 4.4X / IK07 |
| ADF version | Marine aluminium alloy AS10GY30 yellow RAL 1003, 166 × 195 × 109 mm, 2.2 kg, Ex II 2 G – Eexd IIC T6, IP56 |
| Gas environment (ADF) | Zone 1 and zone 2, surface classification T6 |
| Temperature | Service -20 °C to +40 °C, storage -40 °C to +85 °C |
| Mounting | Wall-mounted, fixed by 4 screws |
Potential alarm AP100 and AP200 (ADF or Standard): documentation
Demande de prix
Ajoutez ce produit à votre demande et envoyez-la en une seule fois depuis le formulaire.
Documentation
Related products
A cathodic protection project?
Our engineers are at your disposal to study your requirements and propose custom-built solutions.
Réponse rapide
Sous 48h
Expertise certifiée
Ingénieurs NACE
Support continu
Maintenance 24/7