FAC100 – Decoupling cell / AC filter
Réf. DIP-033
FAC100 decoupling cell: blocks the cathodic protection DC current between two structures while letting AC through. Nominal current 32 or 40 A AC. Non-ATEX.
Description
The FAC100 decouples two earthing systems: it blocks the cathodic protection DC currents between two structures while letting the alternating currents through. The nominal AC current is, depending on the version, 32 or 40 A.
The F100 AC filter consists of a 33,000 µF / 63 V capacitor bank, a steel enclosure 20 × 2 × 15 cm, surge protection and a 100 mV / 20 A measurement shunt with two plugs. As an option, it can be integrated into a measurement point and coupled to a box (HO7RN-F cable 1×10 mm² or 2×10 mm²). A versatile piece of equipment suited to harsh industrial environments, it is not usable in an ATEX zone (use the FAC200 or equivalent instead).
Caractéristiques techniques
| Function | DC decoupling / AC pass-through between structures |
| Nominal AC current | 32 or 40 A depending on version |
| Capacitors | 33,000 µF / 63 V |
| Measurement shunt | 100 mV / 20 A |
| Enclosure | Steel 20 × 2 × 15 cm |
| Protection | Against surges |
| Connection | HO7RN-F cable 1×10 or 2×10 mm² |
| Limitation | Not usable in ATEX zone (see FAC200) |
Documentation
Demande de prix
Ajoutez ce produit à votre demande et envoyez-la en une seule fois depuis le formulaire.
Documentation
A cathodic protection project?
Our engineers are at your disposal to study your requirements and propose custom-built solutions.
Réponse rapide
Sous 48h
Expertise certifiée
Ingénieurs NACE
Support continu
Maintenance 24/7